1. The vortex flowmeter reasonably selects the installation site and environment.
Avoid strong power equipment, high-frequency equipment, strong power switch equipment; avoid the influence of high-temperature heat source and radiation source, avoid strong vibration places and strong corrosive environment, and consider installation and maintenance.
2. There must be enough straight pipe sections upstream and downstream of the vortex flowmeter.
If there are two 90s on the same plane upstream of the sensor mounting point. Elbows: upstream straight pipe section ≥25D, downstream straight pipe section ≥5D. If there are two 90s on the different planes upstream of the sensor mounting point. For elbows, the upstream straight pipe section is ≥40D, and the downstream straight pipe section is ≥5D. The regulating valve should be installed outside the 5D downstream of the sensor. If it must be installed upstream of the sensor, the straight pipe section upstream of the sensor should be no less than 50D, and the downstream should be no less than 5D.
3. The installation of the vortex flowmeter on the horizontal pipe is the most common installation method for the flow sensor.
When measuring the gas flow rate, if the measured gas contains a small amount of liquid, the sensor should be installed at a higher position in the pipeline. When measuring the liquid flow rate, if the measured liquid contains a small amount of gas, the sensor should be installed in the lower part of the pipeline.
4. Installation of the vortex flowmeter sensor in a vertical pipe.
When measuring gas flow, the sensor can be mounted on a vertical pipe with unlimited flow. If the gas to be measured contains a small amount of liquid, the gas flow should be from bottom to top. When measuring the flow of liquid, the flow of liquid should be from bottom to top: this does not add extra weight to the probe.
5. The vortex flowmeter pipeline adopts vibration reduction measures.
The sensor should be avoided as far as possible on the pipe with strong vibration, especially lateral vibration. If it is necessary to install, vibration damping measures must be taken. Pipe fastening devices are installed at the upstream and downstream 2D ​​of the sensor, and anti-vibration pads are added.
6. The vortex flowmeter sensor is flipped in the horizontal pipe.
This installation method is generally not recommended. This method of installation is not suitable for measuring general gases and superheated steam. It can be used to measure saturated steam and is suitable for measuring high temperature liquids or when cleaning pipes frequently.
7. The vortex flowmeter sensor is installed on the pipeline with insulation layer.
When measuring high temperature steam, the insulation layer should not exceed one third of the height of the bracket.
8. Selection of pressure measuring point and temperature measuring point of vortex flowmeter.
According to the needs of the measurement, when measuring the pressure and temperature near the sensor, the pressure measurement point should be 3-5D downstream of the sensor, and the temperature measurement point should be 6-8D downstream of the sensor.
9. The vortex flowmeter sensor is mounted on the side of the horizontal pipe.
Regardless of the fluid being measured, the sensor can be mounted sideways on a horizontal pipe, especially for superheated steam, saturated steam and cryogenic liquids. If conditions permit side-loading, the temperature of the fluid has less effect on the amplifier.
Flame Treating Machine,Unscrambler Machine,Uv Curing Machine,Quality Inspection Machine,Flame Treating Equipment,Unscrambler Equipment,Uv Curing Equipment,Quality Inspection Equipment,Visual quality inspection,Flame Treatment Equipment,treatment machine
GIG (DONGGUAN) CO., LTD , https://www.sennyprinter.com